Compliance knowledge
Fire NOC guidelines
A clear summary of the Fire NOC issuance guidelines for residential Group A, used by our estimator. Always verify final requirements with the local fire authority.
Key reforms at a glance
The guidelines rationalise applicability so smaller, lower-risk buildings are not forced into disproportionate systems.
Where these rules apply
Residential buildings (Group A), including lodging, dwellings, dormitories, apartments, hotels and eateries / dhabas / food courts.
- Homestays are exempted from Fire NOC
- Other occupancies follow NBC Part 4 until notified
- A-1, A-2 and A-6 buildings above 18 m are not permitted (Note 3)
Group A subdivisions
- A-1 — Lodging & rooming houses (inns, motels, guest houses, B&B)
- A-2 — One or two family private dwellings
- A-3 — Dormitories
- A-4 — Apartment houses
- A-5 — Hotels / starred hotels
- A-6 — Eateries, dhabas & food courts
Table 7 — installation matrix (summary)
Minimum fire-fighting installations by case. R = Required, NR = Not required.
| Occupancy case | Extinguisher | Hose reel | Riser / hydrant | Sprinkler / alarm | Water & pump |
|---|---|---|---|---|---|
| Lodging ≤ 15 rooms, < 18 m | R | NR | NR | Sprinkler if basement > 200 m² | Terrace tank if basement rule |
| Lodging 16–30 rooms | R | R | NR | Basement sprinkler note | 5,000 L + 450 LPM (+ basement boost) |
| Apartment / dorm < 18 m | R | R | NR | Basement sprinkler note | 5,000 L · 450 LPM |
| Apartment 18–35 m | R | R | Downcomer | Sprinkler + MOEFA | 25,000 L · 900 LPM |
| Apartment 35–45 m | R | R | Wet riser | Sprinkler + MOEFA | UG 75,000 · terrace 5,000 · Note 10 pumps |
| Apartment 45–60 m | R | R | Wet riser + yard hydrant | Sprinkler + MOEFA | UG 1,00,000 · terrace 10,000 · Note 11 |
| Apartment > 60 m | R | R | Wet riser + yard hydrant | Sprinkler + MOEFA + auto detection | UG 1,50,000 · Note 12–13 pumps |
| Hotel < 18 m, area ≤ 400 m² | R | R | NR | MOEFA · basement sprinkler note | 5,000 L · 450 LPM |
| Hotel < 18 m, 400–1000 m² | R | R | Wet riser if > G+1 | Sprinkler + MOEFA + detection | UG min 50,000 · terrace 10,000 |
| Eatery ≤ 400 m² | R | NR | NR | Basement sprinkler note | As basement notes |
Provisional NOC
After recommendations are issued, a 6-month provisional NOC can be granted, with further extension pathways (including a penalty route). Owners may use it to secure finance for compliance works. An undertaking is required that the Fire Department is not liable for incidents during non-compliance.
Water storage flexibility
Cluster static tanks (3–5 lakh litres) may be used where individual tanks are impractical. Ground-level tanks are allowed where terrace slabs cannot take overhead tank loads in hilly terrain.
NBC Part 4 — how we use it
NBC 2016 Part 4 (Fire and Life Safety) covers fire prevention, life safety / means of egress, fire protection installations and occupancy-wise extras. Our public pages summarise only what owners need for scoping; the estimator’s primary rule engine is the local Fire NOC Table 7 for Group A. Final design remains an engineering exercise — the code sets a reasonable minimum, not absolute safety.